Voltage Drop Calculator
Estimate the voltage drop along a copper or aluminium cable run. Choose single-phase/DC or three-phase, enter the supply voltage, load current, one-way cable length and conductor size in AWG or mm², and the calculator gives the drop in volts and as a percentage, the voltage at the load and the conductor resistance, with a quick check against the common 3% guideline.
Voltage drop calculator
On this calculator: Ctrl+Enter copies the result, Shift+Alt+L copies a link to the current inputs, Shift+Alt+R resets, Shift+Alt+P opens Print / Save PDF. These shortcuts do not run while you type in a field, except Ctrl+Enter.
Saved results on this device
Stored only in this browser, not on our servers.
How to use the voltage drop calculator
- Choose the system. Single-phase (or DC) for most household circuits; three-phase for balanced three-phase loads.
- Enter voltage and current. Enter the nominal supply voltage and the load current in amps.
- Enter the cable length. Enter the one-way length from the supply to the load. The calculator accounts for the return conductor.
- Choose conductor and temperature. Pick copper or aluminium, the conductor size, and the conductor operating temperature (75 °C or 70 °C are common design values; 20 °C gives the cold resistance).
Every cable has resistance, so some voltage is lost along its length. On long runs to garages, garden lighting, pumps, EV chargers or workshops, that loss can be large enough to dim lights, slow motors or trip equipment. This calculator gives a quick estimate of the drop so you can see whether a larger cable is worth discussing with your electrician.
Safety first. Electrical work is regulated in most places and can be dangerous. Use this tool for planning and understanding, and have a qualified, licensed electrician design and install circuits.
The formula explained
ρ(T) = ρ₂₀ × [1 + α × (T − 20 °C)]
R per metre = ρ(T) ÷ Area
Single-phase / DC: Vd = 2 × L × I × R
Three-phase: Vd = √3 × L × I × R
Percent drop = Vd ÷ Supply voltage × 100
Constants used. Copper resistivity at 20 °C is 1.7241 × 10⁻⁸ Ω·m (the International Annealed Copper Standard, published in NBS Handbook 100) with a temperature coefficient of 0.00393 per °C. Aluminium is taken as 61% IACS (2.8264 × 10⁻⁸ Ω·m) with a coefficient of 0.00403.
AWG sizes are converted to mm² using the standard AWG diameter formula: d = 0.127 mm × 92^((36 − n) ÷ 39). For example, 12 AWG = 3.31 mm² and 10 AWG = 5.26 mm².
Worked examples
Example 1: US garage circuit
120 V single-phase, 16 A, 100 ft one way, 12 AWG copper at 75 °C:
- Resistance: 6.337 Ω/km per conductor.
- Vd = 2 × 30.48 m × 16 A × 0.006337 Ω/m = 6.18 V.
- Percent: 6.18 ÷ 120 = 5.15%, above the 3% guideline.
With 10 AWG, the drop falls to 3.89 V (3.24%), still slightly above 3%. A longer run or a larger load would push toward 8 AWG.
Example 2: UK radial circuit
230 V single-phase, 16 A, 30 m of 2.5 mm² copper:
- At 20 °C: 6.62 V (2.88%).
- At 70 °C operating temperature: 7.92 V (3.44%).
This shows why the conductor temperature matters: BS 7671 tables use resistance at operating temperature.
Example 3: Australian three-phase supply
400 V three-phase, 32 A, 50 m of 6 mm² copper at 75 °C: 9.68 V (2.42%).
Copper resistance by size
Calculated with the constants above (resistance of one conductor, Ω per km):
| Size | mm² | at 20 °C | at 75 °C |
|---|---|---|---|
| 14 AWG | 2.08 | 8.29 | 10.08 |
| 12 AWG | 3.31 | 5.21 | 6.34 |
| 10 AWG | 5.26 | 3.28 | 3.99 |
| 8 AWG | 8.37 | 2.06 | 2.51 |
| 1.5 mm² | 1.50 | 11.49 | 13.98 |
| 2.5 mm² | 2.50 | 6.90 | 8.39 |
| 4 mm² | 4.00 | 4.31 | 5.24 |
| 6 mm² | 6.00 | 2.87 | 3.49 |
| 10 mm² | 10.00 | 1.72 | 2.10 |
To convert to Ω per 1,000 ft, multiply by 0.3048.
Regional notes: US, UK, Australia and Canada
United States. The National Electrical Code (NFPA 70) includes informational notes suggesting a maximum of 3% voltage drop on branch circuits and 5% overall. These are recommendations rather than mandatory rules in most cases, but some codes and equipment instructions make them requirements. Typical residential voltage is 120/240 V.
United Kingdom. BS 7671 (the IET Wiring Regulations) Appendix 4 gives maximum voltage drops for installations supplied from a public low-voltage network: 3% for lighting and 5% for other uses. Typical supply voltage is 230 V single-phase or 400 V three-phase.
Australia. AS/NZS 3000 (the Wiring Rules) limits voltage drop from the point of supply to any point in the installation, commonly 5%. Supply voltage is 230 V single-phase, 400 V three-phase.
Canada. The Canadian Electrical Code (CSA C22.1) sets voltage drop limits for branch circuits and feeders. Residential supply is 120/240 V. Sizes are given in AWG.
Tips and common mistakes
- Use the one-way length, not the round trip.
- Use the real load current, not the breaker rating, for a realistic estimate; designers often check at the breaker rating as a worst case.
- Account for temperature. Hot conductors have more resistance.
- Long low-voltage runs (12 V or 24 V lighting) are very sensitive to drop; a small current at low voltage can lose a large percentage.
- Voltage drop is only one check. Ampacity, fault current, protective devices and installation method also matter.
Related tools
Converting a cable run measured in feet and inches? Use the feet and inches to mm converter. Running power to a deck or fence line? See the deck calculator and the fence calculator.
Frequently asked questions
How do I calculate voltage drop?
For single-phase or DC, Vd = 2 × length × current × resistance per unit length. For three-phase, replace 2 with √3 (1.732). Resistance depends on conductor material, size and temperature.
What is an acceptable voltage drop?
A common guideline in the US NEC informational notes is 3% for a branch circuit and 5% for feeder plus branch. In the UK, BS 7671 gives 3% for lighting and 5% for other uses from a public supply. Check the rules that apply to you.
What is the voltage drop on 12 AWG wire over 100 feet?
At 16 A and 120 V, a 100 ft one-way run of 12 AWG copper at 75 °C drops about 6.2 V (5.2%). Upsizing to 10 AWG reduces it to about 3.9 V (3.2%).
Why is the cable length one way?
Current flows out on one conductor and back on another, so the formula doubles the one-way length for single-phase circuits.
Does temperature affect voltage drop?
Yes. Copper's resistance rises about 0.39% per °C. A cable at 70 °C has about 20% more resistance than at 20 °C.
Copper or aluminium?
Aluminium has about 1.6 times the resistance of copper for the same cross-section, so it needs a larger size for the same voltage drop.
Does this calculator size cables?
No. It estimates voltage drop only. Cable size must also meet current-carrying capacity, protective device, installation method and fault requirements in your wiring rules.
Is this accurate for large AC cables?
It is a resistive estimate that ignores reactance. For large AC conductors, especially above about 50 mm² or 1/0 AWG, the true drop is somewhat higher.
Related calculators
Feet and Inches to mm Converter
Feet, inches and fractions to mm and back.
Fence Calculator
Posts, panels, rails, pickets and post concrete.
Decking Calculator
Deck boards, joists and screws for a deck.
Insulation Calculator
Layers and packs to reach a target R-value or RSI.
Ohm’s Law Calculator – Voltage, Current, Resistance and Power
Solve V, I, R and P from any valid pair, using V = I × R and P = V × I.
Voltage Divider Calculator – Vin, R1, R2 and Optional Load
DC voltage divider with optional load: Vout from Vin, R1 and R2.
Sources and references
About this calculator
Written and maintained by Rashid Mehmood, founder of CalcTen. The formulas are unit-tested against hand-worked examples, and the content is reviewed whenever product sizes or guidance change. Last updated and reviewed 1 November 2026. See our editorial policy. If you spot a mistake, report it.
Results are estimates for planning and ordering. Always check product labels, supplier advice and local building codes, and consult a qualified professional for structural work. Read the disclaimer.